COMPACT DRY-TYPE ISOLATION TRANSFORMER

Compact Power Transformer

Series: CPT Series

The CPT Series Compact Power Transformer combines galvanic isolation, voltage conversion and a reduced installation footprint for industrial panels, commercial power rooms and containerized systems. Cast-resin windings, selectable AN or AF cooling and project-specific terminals let engineers match electrical duty, ventilation and access constraints without oversizing the enclosure.

  • Rated Power100 kVA–12 MVA
  • Rated VoltageUp To 35 kV
  • Primary ApplicationSpace-Constrained AC Power Isolation
  • CoolingAN Or AF
  • MOQ1 Unit
  • CustomizationVoltage, Impedance, Vector Group, Enclosure And Footprint

CONFIGURATION DECISION

Compact Footprint Configuration Guide

Choose the cooling and enclosure arrangement together. Reducing external dimensions without preserving air paths and service access can increase temperature rise and maintenance time.

ConfigurationSpecificationImpact And TradeoffBest Fit
Open-Frame ANNatural-Air Cooling, No Outer EnclosureLowest auxiliary power and fewest moving parts. Requires a clean indoor room and more open air clearance.Dedicated electrical rooms with stable ventilation.
Enclosed ANNatural-Air Cooling With Louvered Protective EnclosureImproves touch and dust protection. The enclosure increases airflow resistance and can enlarge the required footprint.Commercial or industrial rooms needing guarded live parts.
Enclosed AFForced-Air Cooling With Fans, Controller And Alarm ContactsSupports higher kVA density in restricted space. Adds fan noise, auxiliary power and maintenance dependence.Containerized systems or rooms with tight footprint limits.
Selection RecommendationUse open-frame AN when the room can provide clean unrestricted airflow. Select an enclosure for personnel or dust protection, and use AF only when the required kVA cannot fit the available footprint under natural cooling. Include fan-failure alarm and the permitted fallback load in the specification.

PRODUCT PHOTOS

Inspect The Core-And-Coil Arrangement From Three Angles

These views show the compact base layout, winding geometry, terminal access and tap locations used to plan enclosure clearances and cable routing.

COMPLETE SPECIFICATIONS

Electrical And Mechanical Ordering Data

Use these series limits to prepare the inquiry. The approved drawing and routine test schedule define the final project configuration.

Product NameCompact Power Transformer
SeriesCPT Series
Product CategoryThree-Phase Dry-Type Isolation Power Transformer
Rated Power100 kVA–12 MVA
Rated Voltage And FrequencyUp To 35 kV; 50/60 Hz
Insulation SystemCast-Resin Insulated Windings With Silicon-Steel Core
Terminals And Vector GroupCopper Busbar Or Cable Terminals; Dyn11, Yyn0 Or Project Vector Group
Applicable StandardIEC 60076-11 / GB/T 1094.11; IEEE Requirements By Project
TraceabilitySerial Number, Material Batch, Process Inspection And Routine Test Report
PackingOne Transformer Per Treated Timber Skid Or Export Crate

APPLICATIONS & EQUIPMENT

Where The Compact Arrangement Adds Value

Select the configuration from the load, grounding, environmental and service-access requirements at the installation point.

01

Industrial Control And Automation

Use between the plant supply and VFD, PLC, test bench or control loads when galvanic isolation and a project-specific voltage ratio are required.

02

Commercial Power And UPS Rooms

Configure the transformer for UPS input or output distribution, sensitive electronic loads and the building grounding scheme; select an enclosure to match the room environment.

03

Containerized And OEM Power Systems

Specify the footprint, terminal direction, cooling path and lifting points for skids, modular substations and equipment packages with restricted access.

MATERIALS & PROCESS

Build The Insulation And Cooling Path As One System

Material batches, coil processing and curing parameters remain traceable through assembly and routine testing.

Core And Windings

Copper conductors, cast-resin insulation and a grain-oriented silicon-steel core.

Manufacturing Process

Core cutting and stacking, coil winding, vacuum resin casting, controlled curing, final assembly and routine electrical testing.

Frame And Enclosure

Powder-coated steel clamps and base with an optional powder-coated protective enclosure.

PERFORMANCE & WORKING CONDITIONS

Set The Rating Against The Real Installation

Capacity and voltage are selected together with cooling, enclosure, altitude, ambient temperature, harmonic duty and available airflow.

100 kVA–12 MVARated Power
Up To 35 kVRated Voltage
50/60 HzFrequency
AN Or AFCooling
Cooling MediumIndoor Clean Air; Optional Enclosure For Dust Or Moisture Control
Standard Ambient-5°C To 40°C
Loading BasisContinuous Nameplate kVA Under The Specified AN Or AF Cooling Condition
Installation BasisAltitude ≤1,000 m; Keep Air Paths Clear And Provide 1 m Access Around Louvered Enclosures

CUSTOMIZATION

Match The Transformer To The Available Space And Duty

Freeze the electrical, mechanical and document interfaces before production to protect fit, temperature rise and delivery timing.

  • Capacity And Voltage
    100 kVA–12 MVA, Up To 35 kV, 50/60 Hz And Project Tap Range
  • Footprint And Interfaces
    Base Dimensions, Terminal Direction, Cable Or Busbar Entry And Lifting Points
  • Electrical Design
    Vector Group, Impedance, Electrostatic Screen And Neutral Arrangement
  • Cooling And Enclosure
    AN Or AF Cooling, Open Frame Or Project-Specific Protective Enclosure
  • Monitoring
    Pt100 Sensors, Temperature Controller, Fan Control, Alarm And Trip Contacts
  • Documentation And Testing
    Approval Drawing, Routine Test Report, FAT Witness Points And Export Documents

USE & SAFETY INSTRUCTIONS

Install, Energize And Maintain The Unit Safely

Use the approved project drawing, nameplate, protection schedule and supplied manual as the controlling documents for the delivered unit.

01

Receiving And Storage

Inspect the enclosure, windings, terminals, accessories and documents for transport damage or moisture. Store indoors on a level base and keep the unit dry until installation.

02

Installation And Earthing

Keep ventilation paths open, secure the base, connect terminals to the approved diagram and bond the core, frame, enclosure, fans and controller to protective earth before energizing.

03

Commissioning And Operation

Verify tap position, phase sequence, insulation, protection settings, fan direction and temperature alarms. Energize unloaded first, then increase load while monitoring sound, current and temperature.

04

Inspection And Maintenance

Isolate and lock out the transformer before work. Remove dust from windings and air ducts, tighten accessible connections, inspect fans and sensors, and record insulation and temperature trends at least annually.

Electrical SafetyDe-energize, isolate, lock out and prove dead before opening the enclosure or touching terminals. Never block cooling airflow, operate a wet unit or change off-circuit taps while energized.

PURCHASING CONDITIONS

Order From One Qualification Unit To A Project Batch

The issued quotation fixes the approved drawing, test scope, payment milestones, delivery basis and destination-specific freight.

  • MOQ1 Unit
  • First-Article PolicyOne Paid First-Article Unit Available For Qualification
  • First-Article Lead Time25–35 Working Days After Drawing Approval And Deposit
  • Batch Lead Time35–55 Working Days After Drawing Approval And Deposit
  • Price BasisEXW Shanghai Or FOB China Port; CIF Available By Destination
  • PackagingMoisture-Barrier Wrap, Treated Timber Skid And Export Crate As Required
  • Payment Terms30% T/T Deposit And 70% Before Shipment
  • Shipping SupportRoad Or Sea Freight With Lifting, Packing And Shipping Documents

PRE-SALES & AFTER-SALES SERVICE

Control The Specification From Proposal To Repeat Order

Engineering, production and service records keep the delivered configuration aligned with the approved technical package.

Before Ordering

Application engineers review load profile, voltage ratio, frequency, impedance, vector group, harmonic duty, enclosure, terminals and footprint before issuing the proposal.

During Production

The order follows drawing approval, material and process control, assembly inspection, routine electrical testing, FAT coordination, packing confirmation and shipment release.

After Delivery

Support covers installation and commissioning guidance, test-report interpretation, troubleshooting, fan or temperature-control spares and repeat-order configuration control.

FACTORY & MANUFACTURER

Trace Design, Production And Testing To The Manufacturer

The manufacturing route links the approved electrical design to material inspection, coil processing, assembly, testing and shipment records.

Technician loading transformer coils into a curing oven

Shanghai Beibian Technology Co., Ltd.

Shanghai Beibian Technology Co., Ltd. designs and manufactures special transformers and power-conversion equipment, with manufacturing locations in Shanghai, Wenzhou and Jinan. The Shanghai contact address is 333 Minta Road, Songjiang District, Shanghai.

  • Contract review and application-specific electrical design
  • Core, coil, insulation, assembly and curing process control
  • Routine electrical tests and OQC before packing
  • PLM, ERP, MES and QMS production-record integration

CERTIFICATES & STANDARDS

Review The Available Compliance Evidence

The supplied certificate copies separate management-system scope, product marking authorization, component recognition and CE compliance.

CE Certificate Of ComplianceIntertek ETL Authorization To MarkUL Component Recognition CertificateISO 9001 Quality Management System Certificate
  • ISO 9001 Quality Management System CertificateProduction And Service Of Dry-Type Rectifier Transformers, Dry-Type Transformers And Test Transformers
  • Intertek ETL Authorization To MarkDry Type Transformer; Related Certification Report 50310621
  • UL Component Recognition CertificateElectrical Insulation System Components
  • CE Certificate Of ComplianceDry Type Rectifier Transformer For Frequency Converter; Expiry 11 April 2027

REQUEST A TECHNICAL QUOTE

Send The Electrical Duty, Space Limit And Quantity