COMPACT DRY-TYPE ISOLATION TRANSFORMER
Compact Power Transformer
Series: CPT Series
The CPT Series Compact Power Transformer combines galvanic isolation, voltage conversion and a reduced installation footprint for industrial panels, commercial power rooms and containerized systems. Cast-resin windings, selectable AN or AF cooling and project-specific terminals let engineers match electrical duty, ventilation and access constraints without oversizing the enclosure.
- Rated Power100 kVA–12 MVA
- Rated VoltageUp To 35 kV
- Primary ApplicationSpace-Constrained AC Power Isolation
- CoolingAN Or AF
- MOQ1 Unit
- CustomizationVoltage, Impedance, Vector Group, Enclosure And Footprint
CONFIGURATION DECISION
Compact Footprint Configuration Guide
Choose the cooling and enclosure arrangement together. Reducing external dimensions without preserving air paths and service access can increase temperature rise and maintenance time.
| Configuration | Specification | Impact And Tradeoff | Best Fit |
|---|---|---|---|
| Open-Frame AN | Natural-Air Cooling, No Outer Enclosure | Lowest auxiliary power and fewest moving parts. Requires a clean indoor room and more open air clearance. | Dedicated electrical rooms with stable ventilation. |
| Enclosed AN | Natural-Air Cooling With Louvered Protective Enclosure | Improves touch and dust protection. The enclosure increases airflow resistance and can enlarge the required footprint. | Commercial or industrial rooms needing guarded live parts. |
| Enclosed AF | Forced-Air Cooling With Fans, Controller And Alarm Contacts | Supports higher kVA density in restricted space. Adds fan noise, auxiliary power and maintenance dependence. | Containerized systems or rooms with tight footprint limits. |
PRODUCT PHOTOS
Inspect The Core-And-Coil Arrangement From Three Angles
These views show the compact base layout, winding geometry, terminal access and tap locations used to plan enclosure clearances and cable routing.
COMPLETE SPECIFICATIONS
Electrical And Mechanical Ordering Data
Use these series limits to prepare the inquiry. The approved drawing and routine test schedule define the final project configuration.
| Product Name | Compact Power Transformer |
|---|---|
| Series | CPT Series |
| Product Category | Three-Phase Dry-Type Isolation Power Transformer |
| Rated Power | 100 kVA–12 MVA |
| Rated Voltage And Frequency | Up To 35 kV; 50/60 Hz |
| Insulation System | Cast-Resin Insulated Windings With Silicon-Steel Core |
| Terminals And Vector Group | Copper Busbar Or Cable Terminals; Dyn11, Yyn0 Or Project Vector Group |
| Applicable Standard | IEC 60076-11 / GB/T 1094.11; IEEE Requirements By Project |
| Traceability | Serial Number, Material Batch, Process Inspection And Routine Test Report |
| Packing | One Transformer Per Treated Timber Skid Or Export Crate |
APPLICATIONS & EQUIPMENT
Where The Compact Arrangement Adds Value
Select the configuration from the load, grounding, environmental and service-access requirements at the installation point.
Industrial Control And Automation
Use between the plant supply and VFD, PLC, test bench or control loads when galvanic isolation and a project-specific voltage ratio are required.
Commercial Power And UPS Rooms
Configure the transformer for UPS input or output distribution, sensitive electronic loads and the building grounding scheme; select an enclosure to match the room environment.
Containerized And OEM Power Systems
Specify the footprint, terminal direction, cooling path and lifting points for skids, modular substations and equipment packages with restricted access.
MATERIALS & PROCESS
Build The Insulation And Cooling Path As One System
Material batches, coil processing and curing parameters remain traceable through assembly and routine testing.
Core And Windings
Copper conductors, cast-resin insulation and a grain-oriented silicon-steel core.
Manufacturing Process
Core cutting and stacking, coil winding, vacuum resin casting, controlled curing, final assembly and routine electrical testing.
Frame And Enclosure
Powder-coated steel clamps and base with an optional powder-coated protective enclosure.
PERFORMANCE & WORKING CONDITIONS
Set The Rating Against The Real Installation
Capacity and voltage are selected together with cooling, enclosure, altitude, ambient temperature, harmonic duty and available airflow.
CUSTOMIZATION
Match The Transformer To The Available Space And Duty
Freeze the electrical, mechanical and document interfaces before production to protect fit, temperature rise and delivery timing.
- Capacity And Voltage
100 kVA–12 MVA, Up To 35 kV, 50/60 Hz And Project Tap Range - Footprint And Interfaces
Base Dimensions, Terminal Direction, Cable Or Busbar Entry And Lifting Points - Electrical Design
Vector Group, Impedance, Electrostatic Screen And Neutral Arrangement
- Cooling And Enclosure
AN Or AF Cooling, Open Frame Or Project-Specific Protective Enclosure - Monitoring
Pt100 Sensors, Temperature Controller, Fan Control, Alarm And Trip Contacts - Documentation And Testing
Approval Drawing, Routine Test Report, FAT Witness Points And Export Documents
USE & SAFETY INSTRUCTIONS
Install, Energize And Maintain The Unit Safely
Use the approved project drawing, nameplate, protection schedule and supplied manual as the controlling documents for the delivered unit.
Receiving And Storage
Inspect the enclosure, windings, terminals, accessories and documents for transport damage or moisture. Store indoors on a level base and keep the unit dry until installation.
Installation And Earthing
Keep ventilation paths open, secure the base, connect terminals to the approved diagram and bond the core, frame, enclosure, fans and controller to protective earth before energizing.
Commissioning And Operation
Verify tap position, phase sequence, insulation, protection settings, fan direction and temperature alarms. Energize unloaded first, then increase load while monitoring sound, current and temperature.
Inspection And Maintenance
Isolate and lock out the transformer before work. Remove dust from windings and air ducts, tighten accessible connections, inspect fans and sensors, and record insulation and temperature trends at least annually.
PURCHASING CONDITIONS
Order From One Qualification Unit To A Project Batch
The issued quotation fixes the approved drawing, test scope, payment milestones, delivery basis and destination-specific freight.
- MOQ1 Unit
- First-Article PolicyOne Paid First-Article Unit Available For Qualification
- First-Article Lead Time25–35 Working Days After Drawing Approval And Deposit
- Batch Lead Time35–55 Working Days After Drawing Approval And Deposit
- Price BasisEXW Shanghai Or FOB China Port; CIF Available By Destination
- PackagingMoisture-Barrier Wrap, Treated Timber Skid And Export Crate As Required
- Payment Terms30% T/T Deposit And 70% Before Shipment
- Shipping SupportRoad Or Sea Freight With Lifting, Packing And Shipping Documents
PRE-SALES & AFTER-SALES SERVICE
Control The Specification From Proposal To Repeat Order
Engineering, production and service records keep the delivered configuration aligned with the approved technical package.
Before Ordering
Application engineers review load profile, voltage ratio, frequency, impedance, vector group, harmonic duty, enclosure, terminals and footprint before issuing the proposal.
During Production
The order follows drawing approval, material and process control, assembly inspection, routine electrical testing, FAT coordination, packing confirmation and shipment release.
After Delivery
Support covers installation and commissioning guidance, test-report interpretation, troubleshooting, fan or temperature-control spares and repeat-order configuration control.
FACTORY & MANUFACTURER
Trace Design, Production And Testing To The Manufacturer
The manufacturing route links the approved electrical design to material inspection, coil processing, assembly, testing and shipment records.

Shanghai Beibian Technology Co., Ltd.
Shanghai Beibian Technology Co., Ltd. designs and manufactures special transformers and power-conversion equipment, with manufacturing locations in Shanghai, Wenzhou and Jinan. The Shanghai contact address is 333 Minta Road, Songjiang District, Shanghai.
- Contract review and application-specific electrical design
- Core, coil, insulation, assembly and curing process control
- Routine electrical tests and OQC before packing
- PLM, ERP, MES and QMS production-record integration
CERTIFICATES & STANDARDS
Review The Available Compliance Evidence
The supplied certificate copies separate management-system scope, product marking authorization, component recognition and CE compliance.




- ISO 9001 Quality Management System CertificateProduction And Service Of Dry-Type Rectifier Transformers, Dry-Type Transformers And Test Transformers
- Intertek ETL Authorization To MarkDry Type Transformer; Related Certification Report 50310621
- UL Component Recognition CertificateElectrical Insulation System Components