BBELC designs compact dry-type transformers for industrial drives and rectifier systems where installation space is limited. Our phase-shifting designs combine voltage conversion, electrical isolation, and multiple AC outputs in one transformer.
Choose a delta-core design for restricted equipment width, a 22/35 kV multi-winding design for a higher-voltage supply, or a transformer matched to a data center rectifier architecture.
Compact Power Transformer
A Narrower Core for Space-Constrained Equipment
BBELC uses a triangular core structure for projects constrained by transformer width. This arrangement supports a compact magnetic assembly while the transformer also provides the winding groups required by the rectifier.
Delta-core designs include a 1,700 kVA unit with a width of 1,260 mm or less (about 49.6 in) and a 4,000 kVA unit with a width of 1,360 mm or less (about 53.5 in). These dimensions give equipment designers a starting point for narrow drive cabinets and electrical layouts.
The final installation envelope also includes the enclosure, terminal connections, and access space. BBELC can adapt the mounting arrangement and connection positions to the equipment layout during project design.
Match the Windings to the Converter
A phase-shifting rectifier transformer changes the supply voltage and provides electrically isolated secondary winding groups. Each group feeds AC power to a rectifier bridge; the rectifier converts that power to DC for the drive or power supply.
The phase displacement between winding groups is selected for the converter's rectification topology. In a coordinated multi-pulse system, those displaced inputs help cancel selected lower-order harmonics at the supply. The resulting input current distortion depends on the rectifier arrangement, load balance, and operating conditions.
Supply voltage and converter topology determine different parts of the design. A 22 or 35 kV supply requires the corresponding primary winding and insulation design. The converter determines the secondary voltages, number of winding groups, phase shifts, and impedance relationships. Matching both sides allows the transformer to fit the electrical system as well as the available space.
Compact Transformer Options
Compare three BBELC designs for industrial power conversion. Their voltage and capacity limits describe each product range; the project design establishes the final rating and dimensions.

Delta-Core Phase-Shifting Rectifier Transformer
A triangular-core design for medium-voltage drives and rectifier equipment with restricted installation width. It combines voltage conversion, isolation, and phase-shifted outputs for the drive's rectifier stages.
- Rated voltageUp to 10 kV
- Rated capacityUp to 4 MVA
- Insulation classF or H

22kV / 35kV High-Voltage Multi-Winding Phase-Shifting Rectifier Transformer
Connects a 22 or 35 kV supply to multiple low-voltage winding groups for large rectifier and variable-frequency drive systems. The winding arrangement provides the phase-displaced supplies required by the converter.
- Supply voltage22 or 35 kV
- Rated capacityUp to 20 MVA
- Insulation classF or H

Phase-Shifting Rectifier Transformer for Data Center Power Systems
Supplies phase-shifted AC to rectifier modules in data center HVDC and UPS front ends. Designs support rectifier architectures serving 240 or 336 V DC systems, with secondary outputs matched to the conversion stage.
- Rated voltageUp to 10 kV
- Rated capacityUp to 3,100 kVA
- Insulation classF or H
Leave Space for Cooling and Connections
A compact dry-type transformer needs an airflow path that carries heat away from its windings and core. Natural air cooling reduces reliance on powered accessories. Forced air cooling can increase heat removal, while adding fan power, controls, and maintenance requirements.
An enclosure changes airflow resistance, so its protection level and ventilation openings form part of the thermal design. In an electrical room, transformer losses also become a heat load for the room's ventilation or cooling system. Ambient temperature, elevation, and the load cycle influence the rating available in that installation.
Allow room for cable or busbar connections, inspection, and cooling-system service around the transformer. The delivery route also needs to accommodate the unit's dimensions, weight, and lifting arrangement. These allowances establish the usable equipment footprint alongside the transformer body dimensions.
Verify the Electrical Design Before Shipment
BBELC tests finished transformers and supplies routine test reports with delivery. Voltage-ratio and phase-displacement checks verify the winding outputs used by the converter. Winding-resistance and loss measurements provide electrical performance data for the supplied unit.
Insulation checks include insulation resistance, applied-voltage and induced-voltage withstand testing, and partial-discharge measurement. The agreed test requirements establish the voltage levels and acceptance criteria for the project.
Factory-witnessed testing and retesting by third-party laboratories are supported. Project documentation and test reports give the equipment integrator the connection information and measured results needed for acceptance.
What Shapes the Project Price?
Compact transformer pricing follows the electrical and mechanical design. Capacity, voltage and insulation level, winding count, impedance, conductor material, enclosure, and cooling equipment all affect materials and manufacturing work. Special dimensions or testing requirements can add engineering and production steps.
Loss requirements affect both purchase price and operating cost. Equipment energized for long periods at light load places more weight on no-load losses. At higher load, winding losses and auxiliary cooling energy contribute more to the cost comparison. Compare loss guarantees at the same operating conditions when evaluating designs.
BBELC quotes against the project's technical requirements and delivery scope. Identify the required accessories, documentation, testing, packing, and delivery destination so the quotation covers the equipment and services needed. The production schedule depends on the final design, materials, and test requirements.